Medium-voltage cables (above 600V) must not share a tray with signal cables under any circumstances. In practice, most industrial installations go beyond the NEC minimum. The fill rules differ significantly between single-conductor cables and multiconductor cables, and between ladder tray and solid-bottom tray. Getting the fill. Question 1: Can mechanical utility piping or tubing containing water or compressed air be installed in cable trays with electrical cables? Answer: No. NEC section 300-8 does not permit. Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and other metal noncurrent-carrying parts that are to serve as grounding conductors, with or without the use of supplementary equipment grounding conductors, shall be effectively bonded where necessary to ensure. Cable tray barriers can be used to separate conductors operating over 600 volts from other conductors in the same tray operating at 600 volts or less. Nor does it apply to the integral parts of electrical equipment [300. 1 (B)]; such. NEC Section 392.